Answer the question the drying plan skips: can the structure power the equipment? Enter the air movers, dehumidifiers, scrubbers, and heaters on the job — amp draws are prefilled with typical values you can override — and you get the total draw, how many 15 A and 20 A circuits the load needs, and the minimum generator when house power won't carry it. Reach for it at setup on any sizable water loss, before the third air mover on one receptacle trips a breaker and costs a night of drying.

Each equipment class draws its nameplate amps: roughly 2.5 A for an axial air mover, 6 A for an LGR dehumidifier, 2 A for an air scrubber, 12 A for a heater. Drying equipment runs continuously — more than three hours — so the NEC continuous-load convention loads each circuit to 80% of its rating: 12 usable amps on a 15 A circuit, 16 on a 20 A. The calculator totals draw per class, divides by usable amps to get circuits per class (units aren't split across circuits), and converts total watts to a minimum generator size at 120 V. Override the amp defaults with your equipment's actual specs; the math is only as good as the nameplates.

Product details

Sold by
Mensuria
Product category
Free field tool · Calculator
Delivery method
Web app · no login
Cost
Free

Highlights

  • Deterministic — the same inputs give the same result, every time.
  • Built for the trade, sized to feed Xactimate line-item quantities.
  • Free — no login, no card.
  • Works from a phone at the loss.

Vendor insights

Mensuria writes a neutral scope built to survive review — every line item sourced to a photo, anything unprovable held back and flagged for you. It never files the estimate; a licensed adjuster confirms every line and stays the adjuster of record. Mensuria is independent and not affiliated with Verisk or Xactimate; “Xactimate-ready” means the worksheet is organized for Quick Entry.

Pricing

This tool is free — no login, no card. The full scope-drafting product is priced below; your first claim is free.

Plan
For
Included
Price
Solo Lite
Part-time / occasional claims
15 claims/mo, then $7/claim
$199 / mo
Solo
Full-time independent adjusters
50 claims/mo, then $4/claim
$299 / mo
Firm
Small teams (3-seat minimum)
Pooled claims, reviewer role, audit trail
$279 / seat · mo
CAT Season Pass
Storm deployments
+150 claims for 30 days, stacks on any plan
$399 one-time

Details

Delivery method

Mensuria is a web app — nothing to install. You work a claim in the browser and export a room-grouped, Xactimate-ready worksheet (codes, quantities, descriptions) organized for Quick Entry. There is no native .ESX import; you key the reviewed line items into Xactimate and stay in control.

Terms and conditions

Use of Mensuria is subject to our Terms of Service. Your first claim is free with no card; paid plans are billed monthly and cancel anytime.

More from this vendor

  • Field photos and a few measurements in; a defensible, Xactimate-ready scope out — every line item sourced to the photo that supports it.

  • Run an estimate you wrote — or a contractor's — past Mensuria for gaps, missed scope, and the companion line items a loss like this usually carries, before you settle. Free for a limited time, no login.

  • 43 calculators and field references for the numbers you work out on site — drying days, roof squares, depreciation, O&P, flood cut, and more. No login, no claim required.

Support

Support

Reach the team at support@mensuria.com . You will hear back from people who have written a scope, not a ticket queue.

Onboarding

Your first claim walks you through capture, draft, review, and export step by step, so you are productive on claim one — no training required.

Refund policy

Monthly plans cancel anytime; the CAT Season Pass is a one-time add-on with no commitment.

Common questions

At a typical 2.5 A per axial air mover, a 15 A circuit at the 80% continuous-load convention (12 usable amps) carries four; a 20 A circuit (16 usable) carries six. Centrifugal units draw more — check the nameplate. The practical failure isn't the arithmetic, it's that the receptacles in one room often share a single circuit with whatever else is on it, so distribute equipment across rooms and circuits and confirm nothing else heavy shares the line.

Total the amps and convert: amps × 120 V ÷ 1,000 = kW, then round up to the next common generator size. Ten air movers (25 A) plus two LGR dehumidifiers (12 A) is 37 A ≈ 4.4 kW — a 5 kW generator with little headroom, so 6.5 kW is the comfortable call. Startup surge on dehumidifier compressors argues for margin above the running load. This calculator does the conversion and suggests the minimum standard size.

The NEC treats loads that run three hours or more as continuous and sizes circuits so they carry no more than 80% of the breaker rating continuously — heat buildup in conductors and breakers is the concern. Drying equipment runs around the clock for days, the definition of continuous. Loading circuits to their full rating invites nuisance trips overnight, and every tripped breaker is drying time lost and a schedule extension to explain. Plan at 80% and the plan survives the night.

Related products and services